This boiler uses electricity as its energy source, converting electrical energy into heat energy through electric heating elements to provide heating, air conditioning, or domestic hot water.
This boiler heats up quickly, is highly efficient, compact, and noiseless. It can be modularly assembled, saving energy and is easy to install and use. It is the latest generation product integrating advanced technologies from both domestic and international sources.
Electric boilers save boiler room space compared to other boilers; using electric boilers eliminates the need for oil storage space and reduces investment in smoking hoods. It employs a thermal storage heating method, with an external hot water storage tank that utilizes off-peak electricity for thermal storage and provides heat from the daytime through the tank, fully utilizing off-peak electricity to reduce heating costs. This boiler uses electricity as its energy source, heating and providing domestic hot water through electric heating elements. It heats up quickly, has high thermal efficiency, is compact, noiseless, modularly designed, energy-saving, easy to install and use, and is the latest generation product integrating advanced technologies from both domestic and international sources. It features a user-friendly interface, is easy to understand, learn, and remember, and is simple and convenient to operate. Various adjustment parameters can be checked, set, and modified through the function keys on the display screen. The system's core PLC boasts high programmability, strong logic processing capabilities, and high operating speed and reliability, employing internationally advanced electrical components. The system can be set to different temperature values according to user requirements to achieve optimal energy-saving effects. The boiler control cabinet lacks protection functions against current interruption, over-temperature, over-pressure, short circuit, leakage, phase loss, and overcurrent, ensuring more stable and safer boiler operation. The boiler can be equipped with an external hot water storage tank, utilizing off-peak electricity at night to heat hot water to 85°C for storage. Heat is then supplied via a heat exchanger, contributing to peak shaving and valley filling of the power grid, making operation more economical. The boiler can achieve variable load functionality: domestic hot water and air conditioning hot water can be provided separately or in combination, achieving multi-purpose use or simultaneous use of multiple units. The boiler uses the cleanest energy source—electricity—truly achieving green environmental protection and zero pollution, maximizing the protection of the human living environment.
WDR Electric Boiler Technical Parameter Table
| project | CWDR | WDR |
| 0.35 | 0.7 | 1.05 | 1.4 | 1.75 | 2.1 | 0.5 | 1 | 2 |
| Rated thermal power /Rated evaporation capacity | MW/ t/h | 0.35 | 0.7 | 1.05 | 1.4 | 1.75 | 2.1 | 0.5 | 1 | 2 |
| Thermal efficiency | % | ≥98 |
| Rated working pressure | Mpa | <0.1 | 1.0 | 1.0 | 1.0 |
| Rated temperature | ℃ | 85/60 | 184 | 184 | 184 |
| power supply | V/Hz | 380/50 | 380/50 | 380/50 | 380/50 |
| Single heating element power | KW | 12 | 12 | 12 | 12 |
| Circulating water volume | M/h | 12 | 25 | / | / | 61 | 74 | / | / | / |
| Heating area | m² | 4375 | 8750 | / | / | 21875 | 26250 | / | / | / |
| heating |
| 60-85℃ |
| / | / | / |
| weight | Kg | 580 | 1150 | 1280 | 1480 | 1680 | 1890 | 900 | 1639 | 1980 |
| Furnace body dimensions | L |
| 1640 | 2370 | 2370 | 2370 | 2370 | 2370 | 2200 | 2530 | 2530 |
| W | mm | 970 | 1020 | 1120 | 1220 | 1320 | 1420 | 1180 | 1380 | 1480 |
| H |
| 1350 | 1550 | 1650 | 1750 | 1850 | 1950 | 1280 | 1480 | 1580 |